Welcome to I TECH SYSTEMS Official Website

Part list and MOC for ROLLER SUPPORT (RLS - 65)

No Description Part No Qty MOC
1 Body ITECHC/047/ROL/01 1 Nos. Graded Cast Iron
2 Roller ITECHC/047/ROL/02 2 Nos. Carbon Steel Cadmium Plated
3 Roller Pin ITECHC/047/ROL/03 2 Nos. SS 316S

RSL – 65 Drum Roller tunnion fabricated from steel , epoxy coated to resist corrosion, Roller are cadmium plated and equipped with bronze bushing for ease of drum rotation. Frame have holes in end to attached to floor via anchor bolts or lag anchors. One set of two tunnions are required for each container.

<
Capacity 2000 Kg
Dimensions 100 x 535 mm D x 110 mm H
Weight 25 Kg per set

PART NO.: A-480

Note : isolation valve and mounting yoke assembly for use with chlorine, sulfur dioxide, gas or liquid.
Material : isolating valve-aluminum silicon bronze yoke-steel

Lifting Beam For CL2 Tonner

This Print is the Property of Chlorotech Eng. Co. It is to be used only for the Purpose for which it was lent and must not be used in any way detrimental to the interest of this company and is subject to return on demand.

MOC for Carbon Steel Pipe for Header line

3/4” CARBON STEEL SCHEDULE 80 ASTM 106 Gr B
Drum gaseous chlorine manifold assembly complete with ¾” schedule 80 seamless carbon steel pipe work and ¾” forged steel 3000 lb fittings painted with yellow chlorine resister rubber paint for chlorine use, with manifold header valve (ISO/3224) 3/4” NPT inlet and 1.030-14 NGO out let.


Reliable, economical chlorine control

The Hach CL17 Chlorine Analyzer uses colorimetric DPD chemistry to continuously monitor water for free or total residual chlorine. This low-cost analyzer provides a dependable and economical alternative to instruments that rely on costly electrodes or complex procedures. Unaffected by even large swings of pH, the CL17 performs an analysis every 2.5 minutes, 24 hours a day.

The CL17 offers both an alarm for manual chlorine feed control and a 4-20 mA output for automatic control of chlorine feed pumps for drinking water, wastewater and other water applications. Set for manual control, the instrument notifies the operator of out-of-limit chlorine levels - and allows manual intervention in the disinfection process as needed. The CL17 can be set for automatic control of chlorine feed pumps using one of two methods:

On-Off Control - Which turns the feed pumps on when chlorine levels fall too low for disinfection and off when levels rise above a pre-set limit.

Proportional Control – Which control the amount of chlorine in proportion to the strength of the CL17’s output signal. This done through the REC MIN and REC MAX keys. For automatic operation, the CL17 has one output control with a range of 4-20 MA, programmable over any portion of the instrument’s 0-5 mg/L range.

The unit is housed in an abs plastic case that is lightweight, shatterproof and corrosion resistant. The case includes built-in mourting bracket that simplify installation. Two windows clearly show chlorine measurements, alarms and reagent levels. A hinged door allows quick access to internal components.

Applications – Water, Wastewater and more
For drinking water application, the CL17 can be used to monitor the raw water stage to facilitate preoxidation, disinfection and the control of taste and odor problems. It can also be used at the
finished Water stage, where residual chlorine levels must be maintained during the distribution phase. For wastewater application, the CL17 has large tubing and fitting along with a self Cleaning By-Pass
Y-Strainer Kit to ensure continuous operation without clogging.

Gas Filter

This Print is the Property of Chlorotech Eng. Co. It is to be used only for the Purpose for which it was lent and must not be used in any way detrimental to the interest of this company and is subject to return on demand.

Data Sheet for Canister Mask - Safety Equipments

(ISI MARK) As Per IS: 8523-1977 License No. CM/L-7024756 of superior quality Non Ageing Chemical Resistant Rubber With Double Reflex Sealing Flaps, Five Point Harness, Panoramic Replaceable Visor, Speech Diaphragm, Self- Demisting Facility, Inhalation and Exhalation Valves to en 148-1 Threading with Rubber Corrugated Tube, Pvc Carrying Strap With Jumbo Canister for Chlorine Max Conc. 20000 PPM 2% With ISI Mark.

>>>
No Description MOC
1 SPINDEL MONAL
2 BUSH FORGED BRASS
3 GLANDE NUT FORGED BRASS
4 GLAND PACKING TEFLON
5 VALVE BODY FORGED SILVER PLATED BRONZE
6 THREADS ¾” BSP TAPER
7 MAKE VANAZ/KOSAN/TECHNO/ASHA

This Print is the Property of Chlorotech Eng. Co. It is to be used only for the Purpose for which it was lent and must not be used in any way detrimental to the interest of this company and is subject to return on demand.




Data Sheet for Chlorine Pressure Gauge

Design for Chlorine Service
Dial Size 65mm to 150mm
Range 0-16 Kg/Cm2
Mounting Bottom Connection mounting on Header Line
Type Chemical sealed diaphragm type with magnetic contact Chamber construction
Top chamber type Brass silver Plated
Bottom chamber type Brass silver Plated, Ti PTFE Padded (100% CL2 Service)
Diaphragm PTFE backed with Silver Foil
Connection type Bottom Connection
Connection size ½” NPT
Type of glass Laminated safety glass
Liquid filled Silicon Oil filled
Dial marking Black




Data Sheet For Water Pressure Gauge

Design for Water Service
Dial Size 65mm to 150mm
Range 0-16 Kg/Cm2
Mounting Direct Mounting/ Surface
Connection type Bottom Connection
Connection size ½” NPT
Type of glass Laminated safety glass
Dial marking Black
Casing Bottom Connection
Connection size +/- 1%
Weather Proof Yes




Data Sheet For Vacuum Pressure Gauge

Design for Chlorine Service
Dial Size 100mm
Range 0-750 mm in Hg
Mounting Panel Mounting
Type Chemical sealed diaphragm type
Top Chamber Type PVC
Bottom Chamber Type PVC
Diaphragm Viton
Connection Type Bottom Connection
Connection Size ¼” NPT
Type of glass Crystal Clear plastic, Snap-fit
Liquid filled Silicon Oil Filled
Dial marking Black
Casing SS case


Technical Data Sheet

Gas to be detected Chlorine gas
Range / Resolution 0 to 20 PPM
Accuracy ±1% of the full scale value.
Sensor type Long life Electrochemical sensor, Imported make
Sensor life Expected 2 year for Electrochemical sensor.
Set point Two independent set point, LO & HI with blinking indication with programmable latch/non-latch facility only for indication purpose. (There is no relay output)
Display Easy- to-read 0.5”, 3.5 digit LCD Display
Setting Setting by 4 keys on front panel i.e. ‘SET / NEXT’, ‘UP’, ‘DOWN’ & ‘TEST / BACK’ keys.
Loop output 4-20mA, with permissible load 750 ohm at 24Vdc, 25mA.
Monitoring i) By display : Shows “Err” indication. Sensor Open/Over Indication
ii) By loop current : Selectable, upscale current : 22mA, Down scale current : 3.6mA to 3.8mA.
Supply Voltage 14VDC to 36VDC, normally 24 VDC, 25mA
Digital filter Select damping factor 1 to 99 to smooth input signal.
Operating ambient Temperature 0 to 50 degree C ± 5%
Relative humidity Below 95%, non condensing.
Sensor Housing P.V.C.
Enclosure Detail FLAMEPROOF , Cast Alluminium alloy, LM-6 / C.I Enclosure, IP-65, As per IS : 2148 – 1981, 145mm (Dia) X 130mm (Height) X 85mm (D) Mounting : Wall Mounting / Stand Mounting, 250 Grams
Model TOX-107-FLP